Work Order Status

View the status of your previously submitted work orders. Work orders submitted prior to 10/2022 will not be updated. If you have a question about the information in this table, please contact Jeremy Lamont at jeremy.lamont@tcatmemphis.edu.

Submission Time
Last Name
Department/Program
Description
Update
Completed
Tech
03/19/2024
Young
Aviation Maintenance Technology
The old drill press and bandsaw in the Structures Lab needs to be removed and the new bandsaws staged in the rear of the lab need to be installed in their place. There is an electrical box on the wall behind the old equipment that the wiring is installed into. The new equipment, I believe, only requires regular power outlets. We need this swap done asap because the students need them for projects.
Removed older equipment and installed new equipment. Waiting for OSB to install outlets.
Yes
McIvor
03/19/2024
Temple
Cosmetology
Shampoo bowl stopped up in theory class.
Unclogged shampoo bowls.
Yes
Harris
03/19/2024
Temple
Cosmetology
Theory classroom very cold.
Adjusted air temp.
Yes
McIvor
03/15/2024
Addison
Dental Assisting
Student has locked her keys in the locker. She needs her lock cut off
Cut lock off.
Yes
McIvor
03/15/2024
Temple
Cosmetology
Old Furniture ( not working) need to be removed from practical floor.
Finished.
Yes
McIvor Bell Harris Lamont
03/14/2024
Moore
Heavy Equipment Technology
The A/C in my office and shop does not work at all.
Adjusted thermostat down.
Yes
Lamont
03/13/2024
Temple
Cosmetology
Outlets hanging from wall , outlets need servicing, May we have stations moved.
Finished.
Yes
McIvor Bell Harris Lamont
03/12/2024
Batts
Aviation Maintenance Technology
The heat in rooms 141 and the front office at the Aviation campus is in the 80's. Please adjust the temp to 72-75 degree. Also, please allow instructor to control the temp in their classrooms.
AHU required reset. Performed by Ricky Batts. Chiller required reset. Performed by Daron Bell. Placed overrides on UV 9 and 2. Manually opened chilled water valve and closed heating water valve on UV2, performed by McIvor, Bell. Controller failure on UV 9 can be overcome by cycling fan. UV2 needs new chilled water actuator and heating water actuator.
Yes
McIvor Bell Lamont
03/09/2024
Farley
Administration
"Good morning, I have several pictures I need to have hung in my area."
Hung up whatever she needed.
Yes
McIvor
03/07/2024
Taylor
Practical Nursing
Good afternoon, the automatic sink in the ladies room on the 4th floor is not working.
Replaced batteries. Repair complete
Yes
McIvor
03/07/2024
Peete
Barbering
"Seven large cabinets need to be removed from the department. On the clinic floor side. thank you"
Cabinets were removed
Yes
McIvor Bell
03/06/2024
Temple
Cosmetology
Wiring Exposed on pole outlets, sockets need to be serviced ( no power}, stations need moving to opposite side of practical classroom
Finished.
Yes
McIvor Bell Harris Lamonr
Updates